Vesta Setup

The RM-1210 relay box, the VS-1108 variable speed control, and the two sensors were connected to the Vesta. All of the signals relating to these devices were given user-friendly names:

  • GH Office Tstat - Vesta discrete input, TRUE if thermostat is calling for heat
  • Mech Room Tstat - Vesta discrete input, TRUE if thermostat is calling for heat
  • Slab Heat Demand - Vesta discrete input, TRUE if greenhouse controller is calling for heat
  • Bench Heat Demand - Vesta discrete input, TRUE if greenhouse controller is calling for heat
  • GH Glycol Hot Supply - Temperature of Glycol being supplied to the greenhouse
  • GH Return To Tank - Temperature of the water being returned to storage
  • P15 GH HX Pump - Vesta variable speed output driving P15

In addition to these inputs and outputs, three internal variables were created to support management of the greenhouse:

  • GH Low Demand - TRUE if any low-temperature greenhouse zone is calling for heat
  • GH Demand - TRUE if any greenhouse zone is calling for heat
  • Greenhouse Target - desired Glycol temperature